Budhi Darma, Made Dwipa and Notes, , S.KM., M.Si, Nengah and Marwati, S.Pd., ST., M.Si., Ni Made (2020) Analisis Efektivitas Instalasi Pengolahan Air Limbah Di Rumah Sakit Bhayangkara Denpasar Tahun 2020. Diploma thesis, Jurusan Kesehatan Lingkungan.
|
Text
BAB I.pdf Download (38kB) | Preview |
|
|
Text
Halaman Depan fix.pdf Download (502kB) | Preview |
|
![]() |
Text
BAB II.pdf Restricted to Repository staff only Download (133kB) | Request a copy |
|
![]() |
Text
BAB III.pdf Restricted to Repository staff only Download (68kB) | Request a copy |
|
![]() |
Text
BAB IV.pdf Restricted to Repository staff only Download (54kB) | Request a copy |
|
![]() |
Text
BAB V.pdf Restricted to Repository staff only Download (151kB) | Request a copy |
|
![]() |
Text
BAB VI.pdf Restricted to Repository staff only Download (28kB) | Request a copy |
|
|
Text
Daftar Pustaka.pdf Download (22kB) | Preview |
|
![]() |
Text
Lampiran.pdf Restricted to Repository staff only Download (1MB) | Request a copy |
|
![]() |
Text
PERNYATAAN PERSETUJUAN PUBLIKASI KARYA ILMIAH.pdf Restricted to Repository staff only Download (1MB) | Request a copy |
Abstract
THE EFFECTIVENESS ANALYSIS OF WASTEWATER TREATMENT PLANTS AT BHAYANGKARA DENPASAR HOSPITAL 2020 ABSTRACT Bhayangkara Denpasar Hospital treats its wastewater at WWTP with a Rotating Biological Contractor treatment system. Across-sectional study design of laboratory research with eight liquid waste samples taken before and after treatment. The results of the study showed that the effectiveness of WWTP reduced the liquid waste temperature 0.11%, TDS 36.67%, TSS 50%, pH 5.75%, NH3N 51.44%, BOD5 79.87%, COD 90.24 % and Total Coliform 84.49%. The conclusion of the study is the parameters of temperature, TDS, TSS, pH, NH3N, BOD5, after processing meet the requirements of the quality standard but the Total Coliform parameters after processing do not meet the requirements in accordance with the quality standard value of the Governor of Bali No. 16 of 2016. The chlorination process at WWTP should pay attention to the contact time, the form of chlorine so that it is expected that the processing effluent for the Total Coliform parameter will be more effective and meet the specified NBM.
Item Type: | Thesis (Diploma) |
---|---|
Uncontrolled Keywords: | Data, Informasi, Perpustakaan |
Subjects: | T Technology > TD Environmental technology. Sanitary engineering |
Divisions: | Jurusan Kesehatan Lingkungan > Prodi D4 |
Depositing User: | BUDHI DARMA MADE DWIPA |
Date Deposited: | 29 Jun 2020 04:27 |
Last Modified: | 29 Jun 2020 04:27 |
URI: | http://repository.poltekkes-denpasar.ac.id/id/eprint/4196 |
Actions (login required)
![]() |
View Item |